Trlon air conditioner manufacturers have silent cooling towers, closed cooling towers and cooling tower noise reduction, maintenance and transformation services.
National Service Hotline National Service Hotline:

4008-8383-95

Your current location:HOME > News > FAQ

FAQ

Precautions for seasonal initial start-up of cooling tower

Author:  Views:  Time:2025-09-26
Precautions for seasonal initial start-up of cooling tower

  Initial and Seasonal LaunchtxqCooling tower noise reduction treatment manufacturer

  Before turning on the device power, check the following:txqCooling tower noise reduction treatment manufacturer

  1. Remove all debris, such as leaves and garbage on the style fence.txqCooling tower noise reduction treatment manufacturer

  2. Rinse the spray tank to remove sediment and dirt.txqCooling tower noise reduction treatment manufacturer

  3. Check if the mechanical float valve is operating flexibly.txqCooling tower noise reduction treatment manufacturer

  4. Check the nozzles of the water distribution system and clean them if necessary. Check if the nozzle orientation is correct. (There is no need to check this item when starting for the first time. The cleaning and orientation setting of the nozzle have been completed before leaving the factory.)txqCooling tower noise reduction treatment manufacturer

  5. Check and ensure that the water blocking plate is securely in place.txqCooling tower noise reduction treatment manufacturer

  6. Adjust the tightness of the fan and water pump screws (if necessary).txqCooling tower noise reduction treatment manufacturer

  7. Lubricate the ventilation fan bearings before seasonal start-up.txqCooling tower noise reduction treatment manufacturer

  8. Rotate the fan blades to ensure normal and unobstructed rotation.txqCooling tower noise reduction treatment manufacturer

  9. Visually inspect the blades of the ventilation fan. Is the gap between the blade tip and the air duct uniform, and is the blade plane flat. The blades should be securely fastened to the fan.txqCooling tower noise reduction treatment manufacturer

  10. If there is stagnant water in the "dead corners" of the system and pipelines, the equipment should be disinfected before the ventilation fan is operated.txqCooling tower noise reduction treatment manufacturer

  11. Fill the spray tank with water until the overflow port is located.txqCooling tower noise reduction treatment manufacturer

  12. For a closed cooling tower, fill the designated medium into the heat exchange coil and use the exhaust hole at the coil inlet to discharge the air from the system before pressurization.txqCooling tower noise reduction treatment manufacturer

  After the device is powered on, check the following:txqCooling tower noise reduction treatment manufacturer

  1. Adjust the mechanical float valve as needed.txqCooling tower noise reduction treatment manufacturer

  2. The water level of the unit's water pan should be at the normal working water level.txqCooling tower noise reduction treatment manufacturer

  3. Check and confirm that the fan rotates in the correct direction.txqCooling tower noise reduction treatment manufacturer

  4. Turn on the spray pump, check and confirm that the impeller rotates in the direction indicated by the arrow on the front cover.txqCooling tower noise reduction treatment manufacturer

  5. Measure the voltage and current of all three-phase power supplies. The current should not exceed the full load current indicated on the motor nameplate by too much, and the service factor should be included in the calculation.txqCooling tower noise reduction treatment manufacturer

  6. Adjust the drain valve to the appropriate flow rate. Please consult with a qualified water treatment company in your local area for the required small sewage flow rate.txqCooling tower noise reduction treatment manufacturer

  7. For more maintenance of fans and water pumps, please refer to "Common Problems and Solutions of Water Pumps" and "Common Problems and Maintenance of Fans"txqCooling tower noise reduction treatment manufacturer

  Attention: Closed cooling towers can only be used for closed pressurized systems. If continuously used in open systems, it will cause corrosion inside the pipes, resulting in a shorter service life of the cooling tower.txqCooling tower noise reduction treatment manufacturer

Article Address:https://www.trlen.com/baike/693.html

News

Contact

Guangdong Trlon Energy-saving Air Conditioning Equipment Co., Ltd.

Contact:Mr. Wang

Free Hotline:4008-8383-95

Company Email:sales@trlon.com

Web Site:https://www.trlen.com/

Company Address: 1916A, Block A, David Donglong Business Building, Longhua, Longhua District, Shenzhen

Trlon WechatClose
alibaba