Trlon air conditioner manufacturers have silent cooling towers, closed cooling towers and cooling tower noise reduction, maintenance and transformation services.
National Service Hotline National Service Hotline:

4008-8383-95

Your current location:HOME > News > FAQ

FAQ

Calculation method of water supply for air conditioning cooling tower

Author:Trlon  Views:  Time:2021-02-23
Calculation method of water supply for air conditioning cooling tower

  Water loss by evaporation (E)LY5Cooling tower noise reduction treatment manufacturer

  E = Q/600 = (T1-T2)×L/600LY5Cooling tower noise reduction treatment manufacturer

  E represents the amount of evaporated water (kg/h);LY5Cooling tower noise reduction treatment manufacturer

  Q represents heat load (Kcal/h);LY5Cooling tower noise reduction treatment manufacturer

  600 represents the latent heat of evaporation of water (Kcal/h);LY5Cooling tower noise reduction treatment manufacturer

  T1 represents the water temperature (℃); T2 represents the water temperature (℃);LY5Cooling tower noise reduction treatment manufacturer

  L represents the circulating water volume (kg/h).LY5Cooling tower noise reduction treatment manufacturer

  Splash loss water (C): The splash loss of the cooling tower is determined by the cooling tower design type, wind speed and other factors. Under normal circumstances, its value is approximately equal to about 0.1% to 0.2% of the circulating water volume.LY5Cooling tower noise reduction treatment manufacturer

  Regular discharge water loss (D): Regular discharge water loss must be determined by factors such as water quality or solid concentration in the water. Generally, it is about 0.3% of the circulating water volume.LY5Cooling tower noise reduction treatment manufacturer

  M=E+C+DLY5Cooling tower noise reduction treatment manufacturer

  Evaporation loss (E), splash loss (C), periodic discharge water loss (D).LY5Cooling tower noise reduction treatment manufacturer

  When the cooling tower is used for air conditioning, the temperature difference is designed to be 5℃. At this time, the make-up water required by the cooling tower is about 2% of the circulating water.LY5Cooling tower noise reduction treatment manufacturer

  Teling cooling tower water drift rate is 0.001%; welcome to inquire us!LY5Cooling tower noise reduction treatment manufacturer

Article Address:https://www.trlen.com/baike/318.html

News

Contact

Guangdong Trlon Energy-saving Air Conditioning Equipment Co., Ltd.

Contact:Mr. Wang

Free Hotline:4008-8383-95

Company Email:sales@trlon.com

Web Site:https://www.trlen.com/

Company Address: 1916A, Block A, David Donglong Business Building, Longhua, Longhua District, Shenzhen

Trlon WechatClose
alibaba