Cooling tower noise control measures

Author:Trlon  Views:  Time:2021-02-26
Cooling tower noise control measures

  Countermeasures for cooling tower noise:

  According to the cooling tower installation conditions, the sound value is somewhat different. If there are noise requirements, please consult the cooling tower manufacturer in advance.

  Regarding the amount of hydrating water:

  1) Evaporation capacity (WE) kg/hqzCCooling tower noise reduction treatment manufacturer

  The circulating water of the cooling tower is constantly evaporating during operation, and the evaporation is calculated by the following formula:qzCCooling tower noise reduction treatment manufacturer

  WEQ/R=(Tw1-Tw2)×L×Cp/RqzCCooling tower noise reduction treatment manufacturer

  When WB=27℃ for general air conditioner, (Tw1-Tw2)=5℃, Q: cooling heat (KJ/h)=(Tw1-Tw2)×L×Cp. R: latent heat of evaporation of water (2520KJ/kg), L: circulating water volume (kg/h), Cp: constant pressure specific heat (4.2KJ/kg°C) to obtain: WE=0.0083×L, that is to say circulating water volume 0.83% of it is evaporated.qzCCooling tower noise reduction treatment manufacturer

  2) Floating water volume (WD) kg/hqzCCooling tower noise reduction treatment manufacturer

  Depending on the structure of the cooling tower and the speed of ventilation, the maximum amount of floating water generally does not exceed the following values:qzCCooling tower noise reduction treatment manufacturer

  Open type, 0.3% of circulating water; closed type, 0.15% of circulating water.qzCCooling tower noise reduction treatment manufacturer

  3) Make-up water volume ΔW (l/min)qzCCooling tower noise reduction treatment manufacturer

  The amount of supplemental water is the sum of the above two items. The specific gravity of water is 1 (kg/l).qzCCooling tower noise reduction treatment manufacturer

  Open air conditioner: 1.13% of circulating water volume; closed type: 0.98% of circulating water volume.qzCCooling tower noise reduction treatment manufacturer

  For safety reasons, 1.5-1.7% of the circulating water volume is generally required.qzCCooling tower noise reduction treatment manufacturer

  4) Volume of sewage WB (kg/h)qzCCooling tower noise reduction treatment manufacturer

  The amount of sewage discharged varies according to the water quality and the concentration ratio. For general air-conditioning, the open type and closed type are the same. The above water volume plus 0.3% of the circulating water volume.qzCCooling tower noise reduction treatment manufacturer

  5) Selection of water supply pipeqzCCooling tower noise reduction treatment manufacturer

  The selection of the water supply pipe is based on the water supply volume and the water supply pressure, and the flow characteristics of the float valve. Especially in the case of a natural falling water tank with low supplemental water pressure, please consult the cooling tower manufacturer in advance.qzCCooling tower noise reduction treatment manufacturer

Article Address:https://www.trlen.com/news/322.html

Colored Contact Form

Get the latest information and prices of cooling towers? We will reply as soon as possible within 24 hours

( Items with * are required)

*name
Company
*Phone
*Message

News

Contact

Guangdong Trlon Energy-saving Air Conditioning Equipment Co., Ltd.

Contact:Mr. Wang

Free Hotline:4008-8383-95

Company Email:sales@trlon.com

Web Site:https://www.trlen.com/

Company Address: 1916A, Block A, David Donglong Business Building, Longhua, Longhua District, Shenzhen

Trlon WechatClose
alibaba