Dust accumulation on cooling tower fan blades can directly lead to an increase in power consumption by changing the operating conditions of the fan and increasing equipment load. The specific impact mechanism and degree are as follows:
1、 Disrupting the airflow structure and increasing wind resistance losses
The accumulation of dust on the surface of the blade will change the original streamlined design of the blade, causing more turbulence when the airflow flows on the blade surface. The originally smooth blades allow the airflow to pass smoothly, but after dust accumulation, the surface roughness increases, and the airflow is obstructed to form vortices, resulting in a significant increase in the resistance of the fan to push the air. To maintain the original airflow (to meet the cooling tower's heat dissipation requirements), the fan motor needs to output greater power to overcome wind resistance, thereby increasing power consumption. According to actual measurements, when the thickness of dust accumulation on the blades reaches 0.5-1mm, the wind resistance can increase by 15% -25%, and the corresponding motor power consumption will increase by 10% -20%.
2、 Breaking the dynamic balance and causing additional energy consumption
The dust accumulation on the blades is usually uneven, with some blades accumulating more dust and others accumulating less, resulting in the center of gravity of the fan rotor deviating from the axis of rotation and disrupting dynamic balance. During operation, an unbalanced rotor will generate periodic vibrations, which on the one hand increases the frictional resistance between the bearing and the shaft sleeve, and the motor needs to consume additional power to overcome frictional losses; On the other hand, vibration can cause looseness in the connection between the fan, tower, and pipeline, further exacerbating airflow disorder and forming a vicious cycle of "vibration energy consumption increase". Long term unbalanced operation not only increases power consumption by 8% -15%, but may also shorten the service life of motors and bearings and increase maintenance costs.
3、 Reduce heat dissipation efficiency and indirectly increase power consumption
Dust accumulation on the blades affects the exhaust efficiency of the fan, resulting in insufficient heat exchange between the cold air and hot water in the cooling tower, and an increase in outlet water temperature. To lower the water temperature to the set value, the chiller unit needs to increase its operating load, and the energy consumption of the chiller unit is directly related to the cooling tower's heat dissipation efficiency - for every 1 ℃ increase in the outlet water temperature of the cooling tower, the chiller unit's power consumption increases by about 3% -5%. This chain reaction of "fan dust accumulation → poor heat dissipation → increased unit load" will lead to a significant increase in the total power consumption of the entire refrigeration system, far exceeding the energy consumption increment of the fan itself.
4、 Suggestions for dust cleaning
Regular cleaning: Stop the machine every 1-2 months to clean the dust accumulation on the blades. Use a high-pressure water gun (pressure controlled within 0.3MPa to avoid damaging the blades) to rinse the surface of the blades, or use a soft bristled brush combined with neutral cleaning agent to wipe, ensuring that the blades return to their original streamlined shape.
Optimize protection: Install dust-proof nets (such as nylon dust-proof nets) at the inlet of the cooling tower to intercept large particles of impurities and willow catkins; Regularly check the dust screen to avoid blockage that affects the air intake.
Status monitoring: Determine whether the blades have accumulated dust through motor current monitoring - if the motor current increases by more than 5% compared to normal under the same operating conditions, it is highly likely that the dust accumulation on the blades is causing wind resistance or imbalance, and it needs to be promptly investigated and cleaned.
In summary, the impact of blade dust accumulation on power consumption is not only reflected in the fan itself, but also indirectly increases the energy consumption of the entire system by affecting the heat dissipation efficiency. It is necessary to pay attention to blade cleaning in daily life to avoid losing out on small things.
Previous topic: Main sources and treatment methods of noise in square cooling towers
Next topic: How to prevent premature damage to cooling tower packing
Company News
line
Article Address:https://www.trlen.com/news/681.html
Guangdong Trlon Energy-saving Air Conditioning Equipment Co., Ltd.
Contact:Mr. Wang
Free Hotline:4008-8383-95
Company Email:sales@trlon.com
Web Site:https://www.trlen.com/
Company Address: 1916A, Block A, David Donglong Business Building, Longhua, Longhua District, Shenzhen